EasyManua.ls Logo

ABB REG650 - Page 171

ABB REG650
728 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
degrees. It can be observed in Figure 77 that the angle reaches 180 degrees when the
complex impedance Z(R, X) crosses the impedance line SE RE. It then changes the
sign, and continues from -180 degrees to 0 degrees, and so on. Figure 77 shows the
rotor (power) angle and the magnitude of Z(R, X) against time for the case from
Figure
76.
0 200 400 600 800 1000 1200 1400
-4
-3
-2
-1
0
1
2
3
4
Time in milliseconds
Impedance Z in Ohm and rotor angle in radian
|Z| in Ohms
angle in rad
normal
load
fault 500 ms
Z(R,X) crossed
the impedance line, Z-line,
connecting points SE - RE
fault
occurrs
Z(R, X) under fault lies
on the impedance line
or near (for 3-ph faults)
Under 3-phase fault
condition rotor angle
of app. ±180 degrees
is measured ...
rotor (power)
angle
|Z|
IEC10000110-1-en.vsd
IEC10000110 V1 EN
Figure 77: Rotor (power) angle and magnitude of the complex impedance Z(R,
X) against the time
In order to be able to fully understand the principles of OOSPPAM, a stable case, that
is, a case where the disturbance does not make a generator to go out-of-step, must be
shown.
1MRK 502 048-UEN A Section 7
Impedance protection
165
Technical manual

Table of Contents

Other manuals for ABB REG650

Related product manuals