op
2
NS
r
TD
t
I
I
=
æ ö
ç ÷
è ø
EQUATION1740-ANSI V1 EN (Equation 515)
where:
t
op
is the operating time in seconds of the negative sequence overcurrent IED
TD is the generator capability constant in seconds
I
NS
is the measured negative sequence current
I
r
is the generator rated current
By defining parameter x equal to maximum continuous negative sequence rating of the
generator in accordance with the following formula
7% 0.07= =x pu
EQUATION1756-ANSI V1 EN (Equation 516)
Equation 515 can be re-written in the following way without changing the value for the
operate time of the negative sequence inverse overcurrent IED:
op
2
NS
r
2
TD
t
I
x I
1
x
×
=
×
æ ö
ç ÷
è ø
EQUATION1741-ANSI V1 EN (Equation 517)
In order to achieve such protection functionality with one CVGAPC functions the
following must be done:
1. Connect three-phase generator currents to one CVGAPC instance (for example,
GF01)
2. Set parameter CurrentInput to value NegSeq
3. Set base current value to the rated generator current in primary amperes
4. Enable one overcurrent step (for example, OC1)
5. Select parameter CurveType_OC1 to value Programmable
Section 12 1MRK 506 369-UUS -
Multipurpose protection
608 Line distance protection REL670 2.2 ANSI