Measurement function application for a 380kV OHL
Single line diagram for this application is given in figure 392:
380kV Busbar
380kV OHL
P Q
800/5 A
ANSI09000039-1-en.vsd
380kV 120V
/
3 3
kV
IED
ANSI09000039 V1 EN
Figure 392: Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated in
figure
392 it is necessary to do the following:
1. Set correctly CT and VT data and phase angle reference channel PhaseAngleRef (see
Section “Setting of the phase reference channel”) using PCM600 for analog input
channels
2. Connect, in PCM600, measurement function to three-phase CT and VT inputs
3. Set under General settings parameters for the Measurement function:
general settings as shown in table 54.
level supervision of active power as shown in table
55.
calibration parameters as shown in table 56.
Section 18 1MRK 506 369-UUS -
Monitoring
822 Line distance protection REL670 2.2 ANSI