UnsucClByCBCheck
, Unsuccessful closing by CB check
The normal setting is
NoCBCheck
. The “auto-reclosing unsuccessful” event is then decided by
a new trip within the reclaim time after the last reclosing shot. If one wants to get the
UNSUCCL (Unsuccessful closing) signal in the case the CB does not respond to the closing
command, CLOSECB, one can set
UnsucClByCBCheck
=
CB Check
and set
tUnsucCl
for instance
to 1.0 s.
Priority
and time
tWaitForMaster
In single CB applications, one sets
Priority
=
None
. At sequential reclosing the function of the
first CB, e.g. near the busbar, is set
Priority
=
High
and for the second CB
Priority
=
Low
. The
maximum waiting time,
tWaitForMaster
of the second CB is set longer than the “auto-
reclosing open time” and a margin for synchrocheck at the first CB. Typical setting is
tWaitForMaster=2sec
.
AutoCont
and
tAutoContWait
, Automatic continuation to the next shot if
the CB is not closed within the set time
The normal setting is
AutoCont
=
Off
. The
tAutoContWait
is the length of time SMBRREC waits
to see if the breaker is closed when
AutoCont
is set to
On
. Normally, the setting can be
tAutoContWait = 2 sec
.
13.3 Apparatus control APC
IP14560-1 v2
13.3.1 Application
IP14931-1 v1
M13443-4 v11
The apparatus control is a function for control and supervising of circuit breakers,
disconnectors, and earthing switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchrocheck, operator
place selection and external or internal blockings.
Figure
104 gives an overview from what places the apparatus control function receive
commands. Commands to an apparatus can be initiated from the Control Centre (CC), the
station HMI or the local HMI on the IED front.
Section 13 1MRK 511 358-UEN A
Control
256
Application manual

Table of Contents