Table 43: General settings parameters for the Measurement function
Setting Short description Selected
value
Comment
Operation Operation Off/On On Function must be
On
PowAmpFact Amplitude factor to scale
power calculations
1.000 Typically no scaling is required
PowAngComp Angle compensation for phase
shift between measured I & U
0.0 Typically no angle compensation is required.
As well here required direction of P & Q
measurement is towards protected object (as
per IED internal default direction)
Mode Selection of measured current
and voltage
Arone Generator VTs are connected between phases
(V-connected)
k Low pass filter coefficient for
power measurement, U and I
0.00 Typically no additional filtering is required
UGenZeroDb Zero point clamping in % of
Ubase
25% Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of
Ibase
3 Set minimum current level to 3%
UBase (set in
Global base)
Base setting for voltage level
in kV
15,65 Set generator rated phase-to-phase voltage
IBase (set in
Global base)
Base setting for current level
in A
3690 Set generator rated current
16.2 Gas medium supervision SSIMG
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
16.2.1 Identification
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Gas medium supervision SSIMG - 63
16.2.2 Application
GUID-A840E38C-CC42-4995-A569-A6092DDB81B2 v5
Gas medium supervision (SSIMG) is used for monitoring the circuit breaker condition. Proper
arc extinction by the compressed gas in the circuit breaker is very important. When the
pressure becomes too low compared to the required value, the circuit breaker operation shall
be blocked to minimize the risk of internal failure. Binary information based on the gas
pressure in the circuit breaker is used as an input signal to the function. The function
generates alarms based on the received information.
16.3 Liquid medium supervision SSIML
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
16.3.1 Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Liquid medium supervision SSIML - 71
1MRK 511 358-UEN A Section 16
Monitoring
385
Application manual