13.9.1 Identification
SEMOD176456-2 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single point generic control 8 signals SPC8GAPC - -
13.9.2 Application
SEMOD176511-4 v4
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands, designed to bring in commands from REMOTE (SCADA) to those parts of the
logic configuration that do not need complicated function blocks that have the capability to
receive commands (for example SCSWI). In this way, simple commands can be sent directly to
the IED outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGGIO function blocks.
PSTO is the universal operator place selector for all control functions. Even if
PSTO can be configured to allow LOCAL or ALL operator positions, the only
functional position usable with the SPC8GAPC function block is REMOTE.
13.9.3 Setting guidelines
SEMOD176518-4 v5
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via
the local HMI or PCM600.
Operation
: turning the function operation
On
/
Off
.
There are two settings for every command output (totally 8):
Latchedx
: decides if the command signal for output
x
is
Latched
(steady) or
Pulsed
.
tPulsex
: if
Latchedx
is set to
Pulsed
, then
tPulsex
will set the length of the pulse (in seconds).
13.10 AutomationBits, command function for DNP3.0
AUTOBITS
SEMOD158589-1 v3
13.10.1 Identification
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
AutomationBits, command function
for DNP3
AUTOBITS - -
13.10.2 Application
SEMOD158637-5 v4
Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600 in order to
get into the configuration the commands coming through the DNP3.0 protocol.The AUTOBITS
function plays the same role as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV
Section 13 1MRK 511 358-UEN A