ABB Relion REC670 - Non-Directional Instantaneous and Definitive Time, Phase and Residual Overcurrent Protection; Non-Directional Inverse Time Delayed Phase and Residual Overcurrent Protection

ABB Relion REC670
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
sr
R
al alreq op ct L
2
pr
r
I
S
E E 5 I R R
I
I
æ ö
³ = × × × + +
ç ÷
è ø
EQUATION1380 V2 EN-US (Equation 131)
where:
I
op
The primary operate value (A)
I
pr
The rated primary CT current (A)
I
sr
The rated secondary CT current (A)
I
r
The rated current of the protection IED (A)
R
ct
The secondary resistance of the CT (W)
R
L
The resistance of the secondary cable and additional load (W). The loop resistance containing the
phase and neutral wires, must be used for faults in solidly earthed systems. The resistance of a single
secondary wire should be used for faults in high impedance earthed systems.
S
R
The burden of an IED current input channel (VA). S
R
=0.020 VA/channel for I
r
=1 A and S
R
=0.150 VA/
channel for I
r
=5 A
22.1.6.2 Non-directional instantaneous and definitive time, phase and residual
overcurrent protection
M11622-3 v5
The CTs must have a rated equivalent limiting secondary e.m.f. E
al
that is larger than or equal
to the required rated equivalent limiting secondary e.m.f. E
alreq
below:
sr
R
al alreq op ct L
2
pr
r
I
S
E E 1,5 I R R
I
I
æ ö
³ = × × × + +
ç ÷
è ø
EQUATION1381 V2 EN-US (Equation 132)
where:
I
op
The primary operate value (A)
I
pr
The rated primary CT current (A)
I
sr
The rated secondary CT current (A)
I
r
The rated current of the protection IED (A)
R
ct
The secondary resistance of the CT (W)
R
L
The resistance of the secondary cable and additional load (W). The loop resistance containing the
phase and neutral wires, must be used for faults in solidly earthed systems. The resistance of a single
secondary wire should be used for faults in high impedance earthed systems.
S
R
The burden of an IED current input channel (VA). S
R
=0.020 VA/channel for I
r
=1 A and S
R
=0.150 VA/
channel for I
r
=5 A
22.1.6.3 Non-directional inverse time delayed phase and residual overcurrent
protection
M11339-3 v5
The requirement according to Equation 133 and Equation 134 does not need to be fulfilled if
the high set instantaneous or definitive time stage is used. In this case Equation is the only
necessary requirement.