IEC05000120-2-en.vsd
SXCBR
(Circuit breaker)
Interlocking
function
block
(Not a LN)
SCSWI
(Switching control)
QCBAY
(Bay control)
SMBRREC
(Auto-
reclosure)
I/O
Trip
Close rel.
Res. req.
S
t
a
r
t
A
R
Close CB
Position
Res. granted
Operator place
selection
SCSWI
(Switching control)
SXSWI
(Disconnector)
Open cmd
Close cmd
Position
SESRSYN
(Synchrocheck & Synchronizer)
SCILO
SCILO
Synchrocheck
OK
QCRSV
(Reservation)
Res. req.
Res.
granted
GAPC
(Generic
Automatic
Process
Control)
Open/Close
Open/Close
Enable
close
Enable
open
Open rel.
Close rel.
Open rel.
SMPPTRC
(Trip logic)
Position
E
n
a
b
l
e
o
p
e
n
E
n
a
b
l
e
c
l
o
s
e
P
o
s
.
f
r
o
m
o
t
h
e
r
b
a
y
s
I/O
Open cmd
Close cmd
(Interlocking)
(Interlocking)
Synchronizing
in progress
IEC05000120 V2 EN-US
Figure 110: Example overview of the interactions between functions in a typical bay
13.3.3 Setting guidelines
M16669-3 v4
The setting parameters for the apparatus control function are set via the local HMI or PCM600.
13.3.3.1 Bay control (QCBAY)
M16670-3 v6
If the parameter
AllPSTOValid
is set to
No priority
, all originators from local and remote are
accepted without any priority.
If the parameter
RemoteIncStation
is set to
Yes
, commands from IEC61850-8-1 clients at both
station and remote level are accepted, when the QCBAY function is in Remote. If set to
No
, the
command LocSta controls which operator place is accepted when QCBAY is in Remote. If
Section 13 1MRK 511 358-UEN A
Control
264
Application manual