Name of input Type Default Description Value when
activated
Value when
deactivated
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the IB16 function block.
15.11 Integer to Boolean 16 conversion with logic node
representation ITBGAPC
SEMOD158419-1 v3
15.11.1 Identification
SEMOD167944-2 v4
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion
with logic node representation
ITBGAPC - -
15.11.2 Application
SEMOD158512-5 v6
Integer to boolean 16 conversion with logic node representation function (ITBGAPC) is used to
transform an integer into a set of 16 boolean signals. ITBGAPC function can receive an integer
from a station computer – for example, over IEC 61850–8–1. This function is very useful when
the user wants to generate logical commands (for selector switches or voltage controllers) by
inputting an integer number. ITBGAPC function has a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function (ITBGAPC) will
transfer an integer with a value between 0 to 65535 communicated via IEC61850 and
connected to the ITBGAPC function block to a combination of activated outputs OUTx where
1≤x≤16.
The values of the different OUTx are according to the Table
38.
If the BLOCK input is activated, it freezes the logical outputs at the last value.
1MRK 511 358-UEN A Section 15
Logic
369
Application manual