controlled. Heavy network load might for instance be the result of malfunctioning equipment
connected to the network.
DOSFRNT, DOSLANAB and DOSLANCD measure the IED load from communication and, if
necessary, limit it for not jeopardizing the IEDs control and protection functionality due to
high CPU load. The function has the following outputs:
LINKUP indicates the Ethernet link status
WARNING indicates that communication (frame rate) is higher than normal
ALARM indicates that the IED limits communication
20.4.2 Setting guidelines
GUID-CE3344E8-539B-47E0-9C19-8239988BDBCF v2
The function does not have any parameters available in the local HMI or PCM600.