MODEINT (integer) ARMode Type of fault 1st shot 2nd-5th shot
2 1/2/3ph
1ph 1ph 3ph
2ph 2ph 3ph
3ph 3ph 3ph
3 1/2ph
1ph 1ph 3ph
2ph 2ph 3ph
3ph ..... .....
4 1ph + 1*2ph
1ph 1ph 3ph
2ph 2ph .....
3ph ..... .....
5 1/2ph + 1*3ph
1ph 1ph 3ph
2ph 2ph 3ph
3ph 3ph .....
6 1ph + 1*2/3ph
1ph 1ph 3ph
2ph 2ph .....
3ph 3ph .....
A start of a new reclosing cycle is blocked during the set “reclaim time” after the selected
number of reclosing shots have been made.
13.2.2.14 External selection of auto-reclose mode
M12391-241 v3
The auto-reclose mode can be selected by use of the available logic function blocks. Below is
an example where the choice of mode is done from a hardware function key in front of the IED
with only 3 phase or 1/3 phase mode, but alternatively there can for example, be a physical
selector switch on the front of the panel which is connected to a binary to integer function
block (BTIGAPC).
The connection example for selection of the auto-reclose mode is shown in
Figure.
IEC07000119 V3 EN-US
Figure 98: Selection of the auto-reclose mode from a hardware functional key in front of
the IED
13.2.2.15 Reclosing reclaim timer
M12391-202 v3
The reclaim timer
tReclaim
defines the time it takes from issue of the reclosing command,
until the reclosing function resets. Should a new trip occur during this time, it is treated as a
continuation of the first fault. The reclaim timer is started when the CB closing command is
given.
1MRK 511 358-UEN A Section 13
Control
245
Application manual