EQUATION1519 V5 EN-US (Equation 111)
where:
U2 is the maximal negative sequence voltage during normal operation conditions, plus a margin of
10...20%
UBase
is the base voltage for the function according to the setting
GlobalBaseSel
The setting of the current limit
3I2<
is in percentage of parameter
IBase
. The setting of
3I2<
must be higher than the normal unbalance current that might exist in the system and can be
calculated according to equation
112.
EQUATION1520 V5 EN-US (Equation 112)
where:
I2 is the maximal negative sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
12.2.3.4 Zero sequence based
M13683-43 v8
The IED setting value
3U0>
is given in percentage of the base voltage
UBase
. The setting of
3U0>
should not be set lower than the value that is calculated according to equation 113.
EQUATION1521 V4 EN-US (Equation 113)
where:
3U0 is the maximal zero sequence voltage during normal operation conditions, plus a margin of 10...20%
UBase is the base voltage for the function according to the setting
GlobalBaseSel
The setting of the current limit
3I0<
is done in percentage of
IBase
. The setting of
3I0<
must
be higher than the normal unbalance current that might exist in the system. The setting can be
calculated according to equation
114.
EQUATION2293 V3 EN-US
(Equation 114)
where:
3I0<
is the maximal zero sequence current during normal operating conditions, plus a margin of 10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel