Forcing of binary inputs and outputs is a convenient way to test wiring in substations as well
as testing configuration logic in the IEDs. Basically it means that all binary inputs and outputs
on the IED I/O modules (BOM, BIM, IOM & SOM) can be forced to arbitrary values.
Central Account Management is an authentication infrastructure that offers a secure solution
for enforcing access control to IEDs and other systems within a substation. This incorporates
management of user accounts, roles and certificates and the distribution of such, a procedure
completely transparent to the user.
Flexible Product Naming allows the customer to use an IED-vendor independent 61850 model
of the IED. This customer model will be used as the IEC 61850 data model, but all other aspects
of the IED will remain unchanged (e.g., names on the local HMI and names in the tools). This
offers significant flexibility to adapt the IED to the customers system and standard solution
2.2 Main protection functions
GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v12.1.1
Table 2: Example of quantities
2 = number of basic instances
0-3 = option quantities
3-A03 = optional function included in packages A03 (refer to ordering details)
IEC 61850 ANSI Function description Bay control
REC670
(Customized)
REC670 (A30)
REC670 (A31)
REC670 (B30)
REC670 (C30)
Differential protection
HZPDIF 87 1Ph high impedance
differential
protection
0-6 3-A02 3-A02 3-A02 6-A07
2.3 Back-up protection functions
GUID-A8D0852F-807F-4442-8730-E44808E194F0 v10
IEC 61850 ANSI Function description Bay control
REC670
(Customized)
REC670 (A30)
REC670 (A31)
REC670 (B30)
REC670 (C30)
Current protection
PHPIOC 50 Instantaneous
phase overcurrent
protection
0-6 1-C51 1-C51 2-C52 2-C53
OC4PTOC
51_67
1)
Four step phase
overcurrent
protection
0-6 1-C51 1-C51 2-C52 2-C53
EFPIOC 50N Instantaneous
residual overcurrent
protection
0-6 1-C51 1-C51 2-C52 2-C53
EF4PTOC 51N
67N
2)
Four step residual
overcurrent
protection
0-6 1-C51 1-C51 2-C52 2-C53
Table continues on next page
Section 2 1MRK 511 358-UEN A
Application
30
Application manual