Table 38: Output signals
Name of OUTx Type Description Value when
activated
Value when
deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) are active
equals 65535. This is the highest integer that can be converted by the ITBGAPC function block.
15.12 Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
15.12.1 Identification
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v2
Function Description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Elapsed time integrator TEIGAPC - -
15.12.2 Application
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
The function TEIGAPC is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is the integration of elapsed time during
the measurement of neutral point voltage or neutral current at earth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow indication
is fixed to 999999.9 seconds.
15.12.3 Setting guidelines
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v2
The settings
tAlarm
and
tWarning
are user settable limits defined in seconds. The achievable
resolution of the settings depends on the level of the values defined.
Section 15 1MRK 511 358-UEN A
Logic
370