A resolution of 10 ms can be achieved when the settings are defined within the range
1.00
second ≤
tAlarm
≤
99 999.99
seconds
1.00
second ≤
tWarning
≤
99 999.99
seconds.
If the values are above this range the resolution becomes lower
99 999.99
seconds ≤
tAlarm
≤
999 999.9
seconds
99 999.99
seconds≤
tWarning
≤
999 999.9
seconds
Note that
tAlarm
and
tWarning
are independent settings, that is, there is no
check if
tAlarm
>
tWarning
.
The limit for the overflow supervision is fixed at 999999.9 seconds.
15.13 Comparator for integer inputs - INTCOMP
15.13.1 Identification
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparison of integer values INTCOMP Int<=>
15.13.2 Application
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
The function gives the possibility to monitor the level of integer values in the system relative
to each other or to a fixed value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.
15.13.3 Setting guidelines
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v1
For proper operation of comparison the set value should be set within the range of ± 2 ×10
9
.
Setting procedure on the IED:
EnaAbs
: This setting is used to select the comparison type between signed and absolute
values.
•
Absolute
: The function will do absolute comparison between input and reference value
•
Signed
: The function will do signed comparison between input and reference value
RefSource
: This setting is used to select the reference source between input and setting for
comparison.
•
REF
: The function will take reference value from input REF
•
SetValue
: The function will take reference value from setting
SetValue
SetValue
: This setting is used to set the reference value for comparison when setting
RefSource
is selected as
SetValue
.
1MRK 511 358-UEN A Section 15
Logic
371
Application manual