ABB Relion REC670 - Comparator for Integer Inputs - INTCOMP; Identification; Application; Setting Guidelines

ABB Relion REC670
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00
second ≤
tAlarm
99 999.99
seconds
1.00
second ≤
tWarning
99 999.99
seconds.
If the values are above this range the resolution becomes lower
99 999.99
seconds ≤
tAlarm
999 999.9
seconds
99 999.99
seconds≤
tWarning
999 999.9
seconds
Note that
tAlarm
and
tWarning
are independent settings, that is, there is no
check if
tAlarm
>
tWarning
.
The limit for the overflow supervision is fixed at 999999.9 seconds.
15.13 Comparator for integer inputs - INTCOMP
15.13.1 Identification
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparison of integer values INTCOMP Int<=>
15.13.2 Application
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
The function gives the possibility to monitor the level of integer values in the system relative
to each other or to a fixed value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.
15.13.3 Setting guidelines
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v1
For proper operation of comparison the set value should be set within the range of ± 2 ×10
9
.
Setting procedure on the IED:
EnaAbs
: This setting is used to select the comparison type between signed and absolute
values.
Absolute
: The function will do absolute comparison between input and reference value
Signed
: The function will do signed comparison between input and reference value
RefSource
: This setting is used to select the reference source between input and setting for
comparison.
REF
: The function will take reference value from input REF
SetValue
: The function will take reference value from setting
SetValue
SetValue
: This setting is used to set the reference value for comparison when setting
RefSource
is selected as
SetValue
.
1MRK 511 358-UEN A Section 15
Logic
371
Application manual