I>
R
Rres
Rl
Rct Rct
Rl
UR
a) Through load situation
b) Through fault situation
UR
UR
c) Internal faults
UR
Protected Object
IEC05000427-2-en.vsd
IEC05000427 V2 EN-US
Figure 33: The high impedance principle for one phase with two current transformer
inputs
1MRK 511 358-UEN A Section 6
Differential protection
91
Application manual