EasyManua.ls Logo

AERMEC VMF-485LINK - Phase 3: Serial Address Setting for HMI;BHP Units

AERMEC VMF-485LINK
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
EN
4.2. PHASE 3 - Serial address setting of the HMI/BHP units
To connect the units to the supervisor, it is necessary to set the correct modbus address to be assigned
to the unit;please note that on VMF-E6, VMF-E5 or MULTICONTROL supervisors, the addresses dedicated
to the chillers are:200, 201, 202, 203. For more information, refer to the documentation of the supervisor
to be used.To set a supervision address on the units, the following steps must be followed:
2020-02-20 08:52 0.0°C 0.0°C
+
-
25°C
(1) From the main screen, press the key for the
HOME screen:
16:41
2017-05-04 Ven
Funzioni Parametri Visual Avviamento Generale
(2) From the HOME screen, press the key to
access the “Start-up menu“:
Avviamento
Funzioni Parametri
(3) From the “Start-up” menu, select the “Func-
tions” sub-menu :
Funzioni (1/4)
Temp di Controllo: T mandata
Valv. 2 Vie in Raff: On
Valv. 2 Vie in Risc: Off
Impostazione Solare: Non Attivo
Serbatoio ACS: Attivo
(4) From the “Functions” sub-menu, scroll the
pages to the “Functions (4/4)“ page:

Table of Contents