Installing, Wiring, and Connecting a –48 VDC PSU
102 7750 SR-a4 and SR-a8 Installation Guide
three lengths of #8 AWG wire, insulated and color-coded according to local safety
code, or #8 AWG jacketed three-conductor cord:
one ground wire, measured to extend from the PSU to the building ground point
or equipment bus ground point
one positive battery cable, measured to extend from the PSU to the positive
battery terminal
one negative battery cable, measured to extend from the PSU to the negative
battery terminal or disconnect device, if used
three single-hole terminal lugs for the three lengths of #8 AWG wire for connection
to the PSU
wire stripping tool
wire crimper
Phillips torque screwdriver
To prepare the PSU end of the ground cable:
Step 1. Using a wire-stripping tool, strip the wire insulation to the length according to the
recommendation of the terminal manufacturer or local safety code (Keys 1and 2 in
Figure 32).
Step 2. Attach the wire to the terminal ring and crimp the ring lug according to the
instructions of the terminal ring manufacturer (Key 3 in Figure 32).
Figure 32: Attaching the Ring Lug to a Ground Cable
Table 44: Ring Lug to Ground Cable Descriptions
Key Description
1 #8 AWG copper wire (see Required tools and hardware)
2 Insulation stripped according to the recommendation of the manufacturer or local
safety code
3 Ring lug (see Required tools and hardware)