Loading...
Installing, Wiring, and Connecting a –48 VDC PSU
104 7750 SR-a4 and SR-a8 Installation Guide
Figure 34: Example of Redundant DC Power Feeds
Connecting –48 VDC Power
24670
6 7
3
4
+
_
5
3
+
_
+Batt A
-Batt A
+Batt B
-Batt B
1
2
Table 46: Redundant DC Power Feeds Description
Key Description
1 DC PSU ground
2 Terminal block
3 Disconnect device
4 DC source A
5 DC source B
6 Battery wire (negative)
7 Battery return wire (positive)
Note:
For a fully redundant power system, you must connect at least two DC PSU modules or
one DC and one AC PSU module.
Wires can be routed to either side of the chassis.