6�4�3 Thermal Management without Fan Tray
When installing the eLimiter+ without a fan tray, 3RU space is required for thermal management. Each shelf requires
a 1RU air space, 1 baffle tray and then an additional 1RU air space, see Figure 7.
Install the first converter shelf and then leave 1 RU of air space directly above the converter shelf. Install a baffle tray
above the air gap, and then leave 1RU of air space between the subsequent converter shelf.
Provide a minimum 3-inch air space between the floor and the bottom of the unit for ventilation.
Figure 7 Thermal management without a fan tray
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1RUAirgap
1RUAirgap
Baffle
1RUAirgap
Baffle
1RUAirgap
eLimiter+
SHELF2
eLimiter+
SHELF2
1RUAirgap
Baffle
1RUAirgap
Baffle
eLimiter+
SHELF3
1RUAirgap
eLimiter+
SHELF3
1RUAirgap
1RUAirgap
eLimiter+
SHELF1
1RUAirgap
eLimiter+
SHELF1
1RUAirgap
eLimiter+
SHELF4
1RUAirgap
Baffle
1RUAirgap
Baffle
1RUAirgap
eLimiter+
SHELF4
1RUAirgap
Baffle
1RUAirgap
eLimiter+
SHELF5
Baffle
1RUAirgap
1RUAirgap
eLimiter+
SHELF5
Baffle
1RUAirgap
1RUAirgap
Baffle
Baffle
1RUAirgap
Baffle
eLimiter+
SHELF6
1RUAirgap
eLimiter+
SHELF6
19"Rack
19"Rack
1RUAirgap
eLimiter+
SHELF7
1RUAirgap
eLimiter+
SHELF7
Floor
Floor
3-inch air space 3-inch air space
FLOOR
FLOOR

Table of Contents