EasyManuals Logo

Alpha Technologies 100VA eLimiter+ User Manual

Default Icon
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
19
0120028-J0 Rev F
6�4�3 Thermal Management without Fan Tray
When installing the eLimiter+ without a fan tray, 3RU space is required for thermal management. Each shelf requires
a 1RU air space, 1 baffle tray and then an additional 1RU air space, see Figure 7.
Install the first converter shelf and then leave 1 RU of air space directly above the converter shelf. Install a baffle tray
above the air gap, and then leave 1RU of air space between the subsequent converter shelf.
Provide a minimum 3-inch air space between the floor and the bottom of the unit for ventilation.
Figure 7 Thermal management without a fan tray
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1RUAirgap
1RUAirgap
Baffle
1RUAirgap
Baffle
1RUAirgap
eLimiter+
SHELF2
eLimiter+
SHELF2
1RUAirgap
Baffle
1RUAirgap
Baffle
eLimiter+
SHELF3
1RUAirgap
eLimiter+
SHELF3
1RUAirgap
1RUAirgap
eLimiter+
SHELF1
1RUAirgap
eLimiter+
SHELF1
1RUAirgap
eLimiter+
SHELF4
1RUAirgap
Baffle
1RUAirgap
Baffle
1RUAirgap
eLimiter+
SHELF4
1RUAirgap
Baffle
1RUAirgap
eLimiter+
SHELF5
Baffle
1RUAirgap
1RUAirgap
eLimiter+
SHELF5
Baffle
1RUAirgap
1RUAirgap
Baffle
Baffle
1RUAirgap
Baffle
eLimiter+
SHELF6
1RUAirgap
eLimiter+
SHELF6
19"Rack
19"Rack
1RUAirgap
eLimiter+
SHELF7
1RUAirgap
eLimiter+
SHELF7
Floor
Floor
3-inch air space 3-inch air space
FLOOR
FLOOR

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Alpha Technologies 100VA eLimiter+ and is the answer not in the manual?

Alpha Technologies 100VA eLimiter+ Specifications

General IconGeneral
BrandAlpha Technologies
Model100VA eLimiter+
CategoryPortable Generator
LanguageEnglish