45
0120028-J0 Rev F
7�4 Troubleshooting the Fan Tray Status LED
LED State Module Status Action
Green
Normal None
Blinking Green
Ambient Temperature < 20 C None
Yellow
Recoverable:
Ambient temperature high
Resets automatically when ambient temperature
reduces to approximately 85°C or below.
Blinking Yellow
Recoverable:
• Input Voltage out of range (High/
Low)
Fan operation is disabled if input voltage is not within the
range of 40-60Vdc.
Non-recoverable:
• Fan Voltage Low
Possible component failure. Replace fan tray.
Red
Fan Fail Replace fan tray.