0120028-J0 Rev F
34
Figure 31 — Channel information for position 6
The icon in the Startup/ Shutdown row indicates whether the LPS channel is powered ON (green) or OFF (black).
Clicking a green icon for a particular channel commands the module to turn the output of that channel OFF.
Clicking a black icon commands the module to turn the output of that channel ON.
The module Startup / Shutdown icon is used to turn all four of modules ON or OFF at the same time.
If the Group Reset switch has been enabled, then the grouped modules will follow the same state as the modules
that are being remotely controlled.
Clicking a row displays a pop-up window with information specific to that LPS (eLimiter+) module and its channels.
Note 1: If the eLimiter+ modules are swapped quickly after acquired by CXCI+ controller,
the logical position in the GUI is not automatically updated to match the new slot posi-
tion. To prevent this from happening, leave the eLimiter+ modules disconnected for long
enough for the CXCI+ to detect they are missing (wait for the LPS Comms Lost alarm to
be raised) before swapping them. In the event that the module position is not updated
for any reason, an inventory update on the GUI or a soft reset on the CXCI+ will solve
the issue.
NOTE:
Note 2: The remote Startup/Shutdown feature using CXCI+ controller is not a direct
replacement for main power switch. This feature is mainly used to facilitate the reset of
any latched channel, to temporarily enable/disable the channel, to synchronize restart of
all group channels, or to clear any fault on the module.
When the channel/module is in shutdown mode, cycling the input supply (by unplug-
ging the module or by power removal) will make the channel/converter active again
when power is restored.
NOTE: