Functional Profiles Supported by the Drive
I/O Profile
Using the I/O profile simplifies PLC programming.
The I/O profile mirrors the use of the terminal strip for control by utilizing 1 bit to control a function.
The I/O profile for the drive can also be used when controlling via a fieldbus.The drive starts up as soon as
the run command is sent.15 bits of the control word (bits 1...15) can be assigned to a specific function.
This profile can be developed for simultaneous control of the drive via:
The terminals
The Modbus control word
The CANopen control word
Ethernet Modbus TCP embedded
The fieldbus module control word
The I/O profile is supported by the drive itself and therefore in turn by all the communication ports
(integrated Modbus, CANopen, Ethernet, PROFIBUS DP ,PROFINET, EtherCAT, and DeviceNet fieldbus
modules).
CiA402 Profile
The drive only starts up following a command sequence.
The control word is standardized.
5 bits of the control word (bits 11...15) can be assigned to a function.
The CiA402 profile is supported by the drive itself and therefore by all the communication ports (Modbus,
CANopen, Ethernet, and PROFIBUS DP, PROFINET, EtherCAT, and DeviceNet).
The drive supports the velocity mode of CiA402 profile.
In the CiA402 profile, there are two modes that are specific to the drive and characterize commands and
references value management:
Separate [Separate] SEP
Not separate [Not separ.] SIm,