Smoke Control Programs
5-43 Infinity Smoke Control Guide
TOC
‘ Return Air Damper
If INFINITY1 FL2RADmp.OVR.Cls then
Fl2.RASDmp = On
Else
If INFINITY1 FL2RADmp.OVR.Opn then
Fl2.RASDmp = Off
Else
If INFINITY1 Zone2.EXH then
Fl2.RASDmp = Off
Else
If INFINITY1 Zone2.PRS then
Fl2.RASDmp = On
Else
If INFINITY1 Zone2.SMK then
Fl2.RASDmp = Off
Else
If INFINITY1 Zone1.SMK or INFINITY1 Zone3.SMK ~
or INFINITY1 Zone4.SMK or INFINITY1 ~
STRWL.SMK then
Fl2.RASDmp = On
Else
Fl2.RASDmp = DefaultDmprPosn
Endif
Endif
Endif
Endif
Endif
Endif
‘ Floor (Zone) 3 Smoke Damper Control
‘ Supply Air Damper
If INFINITY1 FL3SADmp.OVR.Cls then
Fl3.SASDmp = On
Else
If INFINITY1 FL3SADmp.OVR.Opn then
Fl3.SASDmp = Off
Else
If INFINITY1 Zone3.EXH then
Fl3.SASDmp = On
Else
If INFINITY1 Zone3.PRS then
Fl3.SASDmp = Off
Else
If INFINITY1 Zone3.SMK then
Fl3.SASDmp = On