Smoke Control Programs
5-44 Infinity Smoke Control Guide
TOC
Else
If INFINITY1 Zone1.SMK or INFINITY1 Zone2.SMK ~
or INFINITY1 Zone4.SMK or INFINITY1 ~
STRWL.SMK then
Fl3.SASDmp = Off
Else
Fl3.SASDmp = DefaultDmprPosn
Endif
Endif
Endif
Endif
Endif
Endif
‘ Return Air Damper
If INFINITY1 FL3RADmp.OVR.Cls then
Fl3.RASDmp = On
Else
If INFINITY1 FL3RADmp.OVR.Opn then
Fl3.RASDmp = Off
Else
If INFINITY1 Zone3.EXH then
Fl3.RASDmp = Off
Else
If INFINITY1 Zone3.PRS then
Fl3.RASDmp = On
Else
If INFINITY1 Zone3.SMK then
Fl3.RASDmp = Off
Else
If INFINITY1 Zone1.SMK or INFINITY1 Zone2.SMK ~
or INFINITY1 Zone4.SMK or INFINITY1 ~
STRWL.SMK then
Fl3.RASDmp = On
Else
Fl3.RASDmp = DefaultDmprPosn
Endif
Endif
Endif
Endif
Endif
Endif
‘ Floor (Zone) 4 Smoke Damper Control
‘ Supply Air Damper