Smoke Control Programs
5-45 Infinity Smoke Control Guide
TOC
If INFINITY1 FL4SADmp.OVR.Cls then
Fl4.SASDmp = On
Else
If INFINITY1 FL4SADmp.OVR.Opn then
Fl4.SASDmp = Off
Else
If INFINITY1 Zone4.EXH then
Fl4.SASDmp = On
Else
If INFINITY1 Zone4.PRS then
Fl4.SASDmp = Off
Else
If INFINITY1 Zone4.SMK then
Fl4.SASDmp = On
Else
If INFINITY1 Zone1.SMK or INFINITY1 Zone2.SMK ~
or INFINITY1 Zone2.SMK or INFINITY1 ~
STRWL.SMK then
Fl4.SASDmp = Off
Else
Fl4.SASDmp = DefaultDmprPosn
Endif
Endif
Endif
Endif
Endif
Endif
‘ Return Air Damper
If INFINITY1 FL4RADmp.OVR.Cls then
Fl4.RASDmp = On
Else
If INFINITY1 FL4RADmp.OVR.Opn then
Fl4.RASDmp = Off
Else
If INFINITY1 Zone4.EXH then
Fl4.RASDmp = Off
Else
If INFINITY1 Zone4.PRS then
Fl4.RASDmp = On
Else
If INFINITY1 Zone4.SMK then
Fl4.RASDmp = Off
Else
If INFINITY1 Zone1.SMK or INFINITY1 Zone2.SMK ~
or INFINITY1 Zone3.SMK or INFINITY1 ~