Example System Points
Andover Controls Corporation B-9
TOC
Table B-3. SCX920S
AHU1
or
AHU2
Points
NAME TYPE DESCRIPTION
SfanSt Input 1
Digital
Supply Fan Differential Pressure Proof Sensor
RfanSt Input 2
Digital
Return Fan Differential Pressure Proof Sensor
OADmp.Opn Input 3
Digital
Outside Air Damper OPEN Proof Sensor
OADmp.Cls Input 4
Digital
Outside Air Damper CLOSED Proof Sensor
EADmp.Opn Input 5
Digital
Exhaust Air Damper OPEN Proof Sensor
EADmp.Cls Input 6
Digital
Exhaust Air Damper CLOSED Proof Sensor
RADmp.Opn Input 7
Digital
Return Air Damper OPEN Proof Sensor
RADmp.Cls Input 8
Digital
Return Air Damper CLOSED Proof Sensor
Sfan Output 1
Digital
Supply Fan Control
Rfan Output 2
Digital
Return Fan Control
OADmp Output 3
TriState
Outside Air Damper Control
EADmp Output 5
TriState
Exhaust Air Damper Control
RADmp Output 7
TriState
Return Air Damper Control
Default.Rfan Numeric Return Fan State when NOT Performing Smoke
Control
Default.Sfan Numeric Supply Fan State when NOT Performing Smoke
Control
DefaultDmpr.EA Numeric Exhaust Air Damper Position when NOT
Performing Smoke Control
DefaultDmpr.OA Numeric Outside Air Damper Position when NOT
Performing Smoke Control
DefaultDmpr.RA Numeric Return Air Damper Position when NOT
Performing Smoke Control
OverrideOn Numeric Flag that Indicates that an Output is Overridden
at the Controller
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Andover Controls Infinity and is the answer not in the manual?

Andover Controls Infinity Specifications

General IconGeneral
BrandAndover Controls
ModelInfinity
CategoryController
LanguageEnglish

Related product manuals