installation &
operating instructions
Design Envelope 4300 and 4380 vertical in-line
pumping unit with integrated controls
52
par. name
setup 1
(sensorless)
setup 2
(external sensor)
setup 3
(external bms)
operation/
display
0-20 Display line 1.1 Small Reference [unit] Reference [unit] Reference [%]
0-21 Display line 1.2 Small Frequency Frequency Frequency
0-22 Display line 1.3 Small Power (kW or hp
depending on site)
Power (kW or hp
depending on site)
Power (kW or hp
depending on site)
0-23 Display line 2 large Feedback 1 [unit] Feedback 1 [unit] Feedback 1 [unit]
0-24 Display line 3 large Sensorless Readout Sensorless Readout No Function
load and
motor
1-00 Configuration mode Closed Loop Closed Loop Open Loop
1-03 Torque charasteristics Variable Torque Variable Torque Variable Torque
1-20 Motor power [kW] Motor nameplate power Motor nameplate power Motor nameplate power
1-22 Motor voltage Motor nameplate Volts Motor nameplate Volts Motor nameplate Volts
1-23 Motor frequency 60 or 50 per nameplate 60 or 50 per nameplate 60 or 50 per nameplate
1-24 Motor current FLA per nameplate FLA per nameplate FLA per nameplate
1-25 Motor nominal speed [rpm] Motor nameplate speed Motor nameplate speed Motor nameplate speed
1-73 Flying start Enabled Enabled Enabled
brakes
2-17 Over-voltage control Enabled Enabled Enabled
reference/
ramps
3-02 Minimum reference 0 No operation 0
3-03 Maximum reference Hdesign [in unit of
mapped perf data]
No operation Max frequency of app
(50 or 60Hz)
3-15 Reference 1 source No operation No operation Analog input 53
3-16 Reference 2 source No operation No operation No operation
3-17 Reference 3 source No operation No operation No operation
3-41 Ramp up time Desired ramp time
(60s typical)
Desired ramp time
(60s typical)
Desired ramp time
(60s typical)
3-42 Ramp down time Desired ramp time
(60s typical)
Desired ramp time
(60s typical)
Desired ramp time
(60s typical)
limits/
warnings
4-10 Motor speed direction Clockwise Clockwise Clockwise
4-11 Motor speed low limit [rpm]
4-12 Motor speed low limit [hz] Min frequency
of application
Min frequency
of application
Min frequency
of application
4-13 Motor speed high limit [rpm]
4-14 Motor speed high limit [hz] Max frequency
of application
Max frequency
of application
Max frequency
of application
digital
in/out
5-01 Terminal 27 mode Input Input Input
5-10 Terminal 18 digital input Start Start Start
5-11 Terminal 19 digital input No operation No operation No operation
5-12 Terminal 27 digital input Run Permissive Run Permissive Run Permissive
5-13 Terminal 29 digital input Jog Jog Jog
5-14 Terminal 32 digital input No operation No operation No operation
5-15 Terminal 33 digital input No operation No operation No operation
5-16 Terminal x30/2 digital input No operation No operation No operation
5-17 Terminal x30/3 digital input No operation No operation No operation
5-18 Terminal x30/4 digital input No operation No operation No operation
5-40 Function relay 1 No operation No operation Alarm
5-40 Function relay 2 No operation No operation Running