Minimum
setting
Factory
setting
Maximum
setting
Shut-down level ˚C 20 80 80
Shut-down level ˚F 68 176 176
Compressor element outlet temperature:
Shut-down warning level ˚C 80 114 120
Shut-down warning level ˚F 176 237 248
Shut-down level ˚C 80 120 120
Shut-down level ˚F 176 248 248
Cooling medium temperature:
Air-cooled compressors (shut-down warning
level)
˚C 0 50 55
Air-cooled compressors (shut-down warning
level)
˚F 32 122 131
Air-cooled compressors, high ambient
version (shut-down warning level)
˚C 0 57 60
Air-cooled compressors, high ambient
version (shut-down warning level)
˚F 32 135 140
Air-cooled compressors (shut-down level) ˚C 0 55 55
Air-cooled compressors (shut-down level) ˚F 32 131 131
Air-cooled compressors, high ambient
version (shut-down level)
˚C 0 60 60
Air-cooled compressors, high ambient
version (shut-down level)
˚F 32 140 140
Water-cooled compressors (shut-down
warning level)
˚C 60 65 90
Water-cooled compressors (shut-down
warning level)
˚F 140 149 194
Water-cooled compressors (shut-down
level)
˚C 60 75 90
Water-cooled compressors (shut-down
level)
˚F 140 167 194
Delay at signal sec 0 20 60
Ambient temperature:
Shut-down warning level ˚C 0 50 55
Shut-down warning level ˚F 32 122 131
Shut-down warning level, high ambient
version
° C 0 57 60
Shut-down warning level, high ambient
version
° F 32 135 140
Shut-down level ˚C 0 55 55
Shut-down level ˚F 32 131 131
Shut-down level, high ambient version ° C 0 60 60
Shut-down level, high ambient version ° F 32 140 140
Delay at signal sec 0 255 255
Oil separator temperature:
Instruction book
2920 1728 05 73