Configuration of tripping time
Required user level: Specialist (4) or higher.
Device configuration M0053
Phase monitoring M0170
Tripping time M0172
Default value: 10.0 s
Setting range: 1.0 300.0 s
Information
Faults in supply voltage (e.g. voltage drops) do not generate a fault signal during the
adjustable tripping time.
114
Actuator controls
Monitoring functions ACV 01.2/ACVExC 01.2 Profibus DP