In an emergency, the EMERGENCY stop button can be used to interrupt the
power supply of the motor control (contactors or thyristors).
Operation mode EMERGENCY stop supersedes all other operation modes.
A new operation command can only be executed once the pressed EMER-
GENCY stop button is released and operation mode EMERGENCY Stop is
cancelled using a Reset command.
Once operation mode EMERGENCY Stop is cancelled (Reset command), in-
coming analogue operation commands (e.g. 0/4 20 mA) or incoming operation
commands via fieldbus will immediately be executed again.
6.6. Operation mode Disabled
See also: Application function <Local controls:enable>
Characteristics
The indication in the top row of the display shows: Disabled
The operation via the push buttons on the local controls is disabled.
Operation mode Disabled is possible in selector switch positions LOCAL and
OFF.
Table 5: Functions depending on the selector switch position:
Function during indication = Disabled
Selector switch is in position
Actuator cannot be operated locallyLocal control (LOCAL)
Local menu operation not possible0 (OFF)
For control via fieldbus interface, the fieldbus disables or enables the operation.
6.7. Operation mode Service
Conditions:
Set selector switch = position Local control (LOCAL) or Remote control (REMOTE).
Display indicates in the first row: Service
Characteristics
The indication in the top row of the display shows: Service
For operation mode Service, a PC or laptop with AUMA CDT service software
is required. AUMA service uses this software (e.g. during commissioning or
maintenance) to perform settings at the actuator controls.
Information
In selector position Local control (LOCAL), press any push button to exit the service
operation mode and to activate operation mode Local.
35
Actuator controls
ACV 01.2/ACVExC 01.2 Profibus DP Operation

Table of Contents

Other manuals for AUMA ACV 01.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA ACV 01.2 and is the answer not in the manual?

AUMA ACV 01.2 Specifications

General IconGeneral
BrandAUMA
ModelACV 01.2
CategoryController
LanguageEnglish

Related product manuals