11. Functions: activate and enable
11.1. Functions: activate
Via Activation menu M0212, functions can be switched on (activated) or off
(deactivated).
Required user level for enabling/disabling: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Information
Some functions require enabling. Only enabled functions are visible and can be ac-
tivated or deactivated.
Table 14:
Enabling requiredMenuFunction
No
M0589EMCY behaviour
No
M0156Timer CLOSE
No
M0206Timer OPEN
Yes
M0158Positioner
No
M0294Operation profile
Yes
M0741Process controller
No
M0857Profibus DP-V2
No
M0573Bluetooth
Yes
M0631Enable LOCAL
Yes
M0770Priority REMOTE
Yes
M0790Auto change-over I/O
Yes
M0663Interlock
No
M0796Torque wrn
Yes
M0851PVST
Yes
M0941By-pass function
No
M1136Maintenance signals
No
M1137Maintenance interval
No
M1884Maintenance reminder
Yes
M1197Limit sw. via CDT/App
No
M1236Fieldbus operation
No
M1650Split range operation
Yes
M1679Automatic deblocking
No
M1842DMF evaluation
No
M1890Mean value curves
No
M1709Com. eval. REMOTE
Yes
M2122Speed profile
11.2. Functions: enable
Via Enabling menu M0179, optional functions can be enabled or disabled.
This menu is visible in the display from user level Specialist (4).
Device configuration M0053
Application functions M0178
Enabling M0179
115
Actuator controls
ACV 01.2/ACVExC 01.2 Profibus DP Functions: activate and enable