EMCY behaviour M0198
EMCY position M0232
Default value: 0.0 %
Setting range: 0.0 100.0 % (from end position OPEN to CLOSED)
9.3.7. EMERGENCY speed
Speed for an EMERGENCY operation.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
Speed EMCY OPEN M1934
Speed EMCY CLOSE M2041
Default value: 6 (rpm)
Setting range: 6 ... 240 (rpm)
The adjustable speed range is indicated on the actuator name plate.
9.3.8. Torque switching: by-pass
If an EMERGENCY operation is initiated, the torque switches can be by-passed
during this operation.
Required access level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass torque M0199
Default value: Off
Setting values:
Off
No by-pass of the torque switching.
On
The signals of the torque switching in the actuator are by-passed.
9.3.9. Motor protection: by-pass
If an EMERGENCY operation is initiated, the motor protection can be by-passed
during this operation.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
Thermal by-pass M0200
Default value: Off
Setting values:
Off
No by-pass of motor protection.
On
The signals of the thermoswitches or the PTC thermistors of the motor winding are
by-passed.
Information
It is not possible to by-pass the motor protection for actuators with explosion protec-
tion.
9.3.10. Stepping mode: by-pass
If an EMERGENCY operation is initiated, stepping mode can be by-passed during
this operation.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
90
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2 Profibus DP

Table of Contents

Other manuals for AUMA ACV 01.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA ACV 01.2 and is the answer not in the manual?

AUMA ACV 01.2 Specifications

General IconGeneral
BrandAUMA
ModelACV 01.2
CategoryController
LanguageEnglish

Related product manuals