EasyManuals Logo

AUMA ACV 01.2 User Manual

AUMA ACV 01.2
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #147 background imageLoading...
Page #147 background image
Faults and Failure
RemedyDescription/causeIndication on display
Check wiring.Loss of signal analogue input 2
Wrn input AIN 2
Check operation command control.
For 3-phase AC current mains, activate phase
monitoring (parameter Adapt rotary dir. M0171).
Check device configuration setting (parameter
Closing rotation M0176).
To delete the fault indication: Disconnect actuator
controls from the mains and perform reboot.
Contrary to the configured direction of rotation and
the active operation command, the motor turns into
the wrong direction.
Incorrect rotary direct.
Motor protection: Fault within converter
Rectifier fault
Table 25:
Not ready REMOTE and Function check (collective signal 04)
RemedyDescription/causeIndication on display
Check operation commands (reset/clear all op-
eration commands and send one operation
command only).
Set parameter Positioner to Function active.
Check setpoint.
Press push button Details to display a list of indi-
vidual indications.
For details, refer to <Individual indications> table.
Collective signal 13:
Possible causes:
Several operation commands (e.g. OPEN and
CLOSE simultaneously, or OPEN and SET-
POINT operation simultaneously)
A setpoint is present and the positioner is not
active
Wrong oper. cmd
Set selector switch to position REMOTE.Selector switch is not in position REMOTE.
Sel. sw. not REMOTE
Exit service software.Operation via service interface (Bluetooth) and
AUMA CDT service software.
Service active
Check setting and status of function <Local controls
enable>.
Actuator is in operation mode Disabled.
Disabled
Enable EMERGENCY stop switch.
Reset EMERGENCY stop state by means of
Reset command.
The EMERGENCY stop switch has been operated.
The motor control power supply (contactors or
thyristors) is disconnected.
EMCY stop active
Detect cause for EMERGENCY signal.
Verify failure source.
Apply +24 V DC at EMERGENCY input.
Operation mode EMERGENCY is active (EMER-
GENCY signal was sent).
0 V are applied at the EMERGENCY input.
EMCY behav. active
Check I/O interface.The actuator is controlled via the I/O interface (par-
allel).
I/O interface
Start motor operation.Manual operation is activated.
Handwheel active
Verify master configurationFieldbus connection available, however no process
data transmission by the master.
FailState fieldbus
Release push button STOP.A local STOP is active.
Push button STOP of local controls is operated.
Local STOP
Check interlock signal.An interlock is active.
Interlock
Check states of main and by-pass valve.By-pass function is interlocked.
Interlock by-pass
Wait until PVST function is complete.Partial Valve Stroke Test (PVST) is active.
PVST active
Table 26:
Individual indications
RemedyIndication on display
Config. warning (Collective signal 06)
Configure analogue inputs AIN 1 or AIN 2, refer to <Input for setpoint position>
Wrn Setpoint Source
Check positioner setting.
Wrn dead bands
Check fieldbus interface configuration.
Wrn Fieldbus config.
Verify torque switching setting.
Torque config. CLOSE
Verify torque switching setting.
Torque config. OPEN
Signal assignment for the indicated digital input (DIN 1 DIN 10) is incorrect.
Reconfigure digital input.
DIN 1 configuration
DIN 10 configuration
147
Actuator controls
ACV 01.2/ACVExC 01.2 Profibus DP Corrective action

Table of Contents

Other manuals for AUMA ACV 01.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA ACV 01.2 and is the answer not in the manual?

AUMA ACV 01.2 Specifications

General IconGeneral
BrandAUMA
ModelACV 01.2
CategoryController
LanguageEnglish

Related product manuals