7 Remote Control
04.09.2016 Mk8 MM Expansion Features Installation and Set-Up Guide Page 119
Address Description Type
30801 Fuel 4 Flow Total Thousands Read analogue
Metric kW/hr, imperial MMBTU/hr
Remainder after whole number of MW/hr or MMBTU x 1000 taken away, x 1000. E.g.
1.5MW/hr gives 500 value and 15.1MMBTU gives 100 value
30802 Fuel 4 Flow Total Millions Read analogue
Metric MW/h, imperial MMBTU
Whole number of MW/hr or MMBTU. E.g. 1.5MW/hr gives 1 value and 15.1MMBTU gives
15 value
30803 Fuel 4 Flow Total Billions Read analogue
Metric GW/hr, imperial MMBTU / 1000
Whole number of GW/hr or MMMBTU E.g. 1.5MW/hr gives 0 value and 15.1MMBTU gives
0 value
30804 VSD 1 Output Read analogue
mA x 10 or V x 10
30805 VSD 1 Input Read analogue
mA x 10 or V x 10
30806 VSD 2 Output Read analogue
mA x 10 or V x 10
30807 VSD 2 Input Read analogue
mA x 10 or V x 10
30808 Channel 7 Position Read analogue
Degrees x 10
Range is -6.0
O
to 96.0
O
30830 Lockout Number Read analogue
0 = System is not in lockout, N = lockout number
30831 Fuel 1 Type Read analogue
0 = Gas, 1 = Oil
Option/ parameter 150 value
30832 Fuel 2 Type Read analogue
0 = Gas, 1 = Oil
Option/parameter 151 value
30833 Fuel 3 Type Read analogue
0 = Gas, 1 = Oil
Option/parameter 152 value
30834 Fuel 4 Type Read analogue
0 = Gas, 1 = Oil
Option/parameter 153 value
30839 Fuel 1 Hours Run Read analogue
Completed hours
30840 Fuel 2 Hours Run Read analogue
Completed hours
30841 Fuel 3 Hours Run Read analogue
Completed hours
30842 Fuel 4 Hours Run Read analogue
Completed hours