Chapter 3: Configuration and Parameters
Page 3–11Stellar
®
SR55 Series Soft Starter User Manual – 1st Ed, Rev F – 09/18/2019
parameTers from “log” menu CaTegory – summary
Summary – Parameters for Touchscreen Setup – “Log” Category
Category – Log
Group Parameter Units Range
Read /
Write
Modbus
Default
Setting
User
Setting
Address Hex
(P16)*
Event Times
for Last
Peak Start
Currents, Last
Temperatures,
Last Overloads
[detailed info
starts page 3–59]
P16�0 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload
hh :
mm
: ss
Time since midnight;
Days since
01/01/1984
Read 38464 9640
GMT
P16�1 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -1
Read 38467 9643
P16�2 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -2
Read 38470 9646
P16�3 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -3
Read 38473 9649
P16�4 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -4
Read 38476 964C
P16�5 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -5
Read 38479 964F
P16�6 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -6
Read 38482 9652
P16�7 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -7
Read 38485 9655
P16�8 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -8
Read 38488 9658
P16�9 – (Event Time)
Last Peak Start Current / Last
Temperature / Last Overload -9
Read 38491 965B
* P16 event times are associated with parameters P18, P20, and P21, and the times are displayed on each of those logs.
(P17)
Trip Log
[detailed info
starts page 3–62]
P17�0 – Last Trip 0 to 65,535 Read 60608 ECC0 0
P17�1 – Last Trip -1 0 to 65,535 Read 60609 ECC1 0
P17�2 – Last Trip -2 0 to 65,535 Read 60610 ECC2 0
P17�3 – Last Trip -3 0 to 65,535 Read 60611 ECC3 0
P17�4 – Last Trip -4 0 to 65,535 Read 60612 ECC4 0
P17�5 – Last Trip -5 0 to 65,535 Read 60613 ECC5 0
P17�6 – Last Trip -6 0 to 65,535 Read 60614 ECC6 0
P17�7 – Last Trip -7 0 to 65,535 Read 60615 ECC7 0
P17�8 – Last Trip -8 0 to 65,535 Read 60616 ECC8 0
P17�9 – Last Trip -9 0 to 65,535 Read 60617 ECC9 0
(P18)
Start Current Log
[detailed info
starts page 3–65]
P18�0 – Last Peak (Start) Current A 0 to 10,000 Read 38400 9600 0
P18�1 – Last Peak Start Current -1 A 0 to 10,000 Read 38402 9602 0
P18�2 – Last Peak Start Current -2 A 0 to 10,000 Read 38404 9604 0
P18�3 – Last Peak Start Current -3 A 0 to 10,000 Read 38406 9606 0
P18�4 – Last Peak Start Current -4 A 0 to 10,000 Read 38408 9608 0
P18�5 – Last Peak Start Current -5 A 0 to 10,000 Read 38410 960A 0
P18�6 – Last Peak Start Current -6 A 0 to 10,000 Read 38412 960C 0
P18�7 – Last Peak Start Current -7 A 0 to 10,000 Read 38414 960E 0
P18�8 – Last Peak Start Current -8 A 0 to 10,000 Read 38416 9610 0
P18�9 – Last Peak Start Current -9 A 0 to 10,000 Read 38418 9612 0