Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
109
of 208
4
P1163
This parameter sets the voltage range of the analog output signal AFM.
When ZP1162 is set to 0, the analog output voltage is directly proportional to the output
frequency of the b maXX
®
1000. With ZP1163 set to 100 %, the maximum output fre-
quency ZP0033 of the b maXX
®
1000 corresponds to +10 V
DC
on the AFM output.
Similarly, if ZP1162 is set to 1, the analog output voltage is directly proportional to the
output current of the b maXX
®
1000. With ZP1163 set to 100 %, then 2.5 times the rated
current corresponds to +10 V
DC
on the AFM output.
For Example: When using the meter with full scale of 5 Volts, adjust ZP1163 to 50 %. If
ZP1162 is set to 0, then 5 V
DC
will correspond to maximum output frequency.
P1164
This parameter selects the mode of the analog voltage output or analog current output.
Besides parameter settings, the voltage/current mode should be used with the switch.
Figure 49: Voltage/current mode setting
P1163
Analoges Ausgangssignal Verstärkung 1 to 200 %
EE Analog output gain 100 %
ON BM_u_AnalogOutputGain 1:1
NOTE
Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10 V,
ZP1163 should be set using the following formula:
ZP1163 = ((meter full scale voltage)/10) x 100%
P1164
AO1 Auswahl Ausgang Mode 0 to 2
EE AO1 terminal mode selection 0
STOP BM_u_TerminalModeSelectionAO1 1:1
Value Meaning
0 AVO1 (analog voltage output)
1 ACO1 by 0 to 20 mA (analog current output)
2 ACO1 by 4 to 20 mA (analog current output)