EasyManua.ls Logo

Baumuller b maXX 1000 - Page 111

Baumuller b maXX 1000
210 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
111
of 208
4
P1168
This parameter sets the function of the AO2 output 0 to +10 V
DC
(ACM is signal ground),
see also ZP1169from page 111.
P1169
This parameter sets the voltage range of the analog output signal AO2.
When ZP1168 is set to 0, the analog output voltage is directly proportional to the output
frequency of the b maXX
®
1000. With ZP1169 set to 100 %, the maximum output fre-
quency ZP0033 of the b maXX
®
1000 corresponds to +10 V
DC
on the AO2 output.
Similarly, if ZP1168 is set to 1, the analog output voltage is directly proportional to the
output current of the b maXX
®
1000. With ZP1169 set to 100%, then 2.5 times the rated
current corresponds to +10 V
DC
on the AO2 output.
For Example: When using the meter with full scale of 5 volts, adjust ZP1169 to 50 %. If
ZP1168 is set to 0, then 5 V
DC
will correspond to maximum output frequency.
P1168
Analoges Ausgangssignal AO2 0 to 1
EE Analog output signal AO2 0
STOP BM_u_AnalogOutputSignal2 1:1
Value Meaning
0 Analog frequency meter (0 to maximum output frequency)
1 Analog current meter (0 to 250 % of rated current)
P1169
Analoges Ausgangssignal Verstärkung AO2 0 to 200 %
EE Analog output gain AO2 100 %
STOP BM_u_AnalogOutputGain AO2 1:1
NOTE
Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10 V,
ZP1169 should be set using the following formula:
ZP1169 = ((meter full scale voltage)/10) x 100%

Table of Contents

Related product manuals