P1368
b maXX
®
1000 reaction when the feedback signals (analog PID feedback or PG (encod-
er) feedback) are abnormal according to ZP1385–.
Complete PID diagram see ZP1369–.
P1369
This is the gain adjustment over the feedback detection value.
Figure 60: Complete PID diagram
P1370
This parameter sets one of the skip frequencies. For further information see ZP1375–.
P1371
This parameter sets one of the skip frequencies. For further information see ZP1375–.
P1368
Antriebsreaktion auf PID Rückführung Fehler 0 to 2
EE Treatment of PID feedback signal error 0
STOP BM_u_PIDFeedbackSignalDetectionTime 1:1 -
Value Meaning
0 Warn and RAMP to stop
1 Warn and COAST to stop
2 Warn and continue operation
P1369
Verstärkung des PID Wertes 0.0 to 10.0
EE Gain over the PID detection value 1.0
STOP BM_u_GainPIDDetectionValue 10:1 -
P1370
Ausblendfrequenz 1 obere Grenze 0.00 to 600.00 Hz
EE Skip frequency 1 upper bound 0.00
STOP BM_u_SkipFrequency1UpperBound 100:1 -
P1371
Ausblendfrequenz 1 untere Grenze 0.00 to 600.00 Hz
EE Skip frequency 1 lower bound 0.00
STOP BM_u_SkipFrequency1LowerBound 100:1 -