Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
137
of 208
4
P1385
This parameter sets the wake up frequency, for further information see ZP1383
P1386
This is the source selection of minimum output frequency when control is by PID.
Complete PID diagram see ZP1369.
P2030
The function of this parameter is to input the password that is set in ZP2031. Input the
correct password here to enable changing parameters. You are limited to a maximum of
3 attempts. After 3 consecutive failed attempts, a blinking „error code 0503
hex
„ will show
up to force the user to restart the b maXX
®
1000 in order to try again to input the correct
password.
P1385
PID Stand-by Einschalt-Frequenz 0.00 to 600.00 Hz
EE PID wake up frequency 0.00
STOP BM_u_WakeUpFrequency 100:1 Hz -
P1386
Minimale PID Ausgangsfrequenz mode 0 to 1
EE Minimum PID output frequency selection 0
STOP BM_u_PIDFeedbackSignalDetectionTime 1:1 -
Value Meaning
0 By PID control
1 By minimum output frequency (ZP0038)
P2030
Passwortschutz Eingabe 0 to 9999
EE Password protect input 0
STOP BM_u_PasswordProtectInput 1:1 -
Value Meaning
0 - 2 Display: times of wrong password
0 to 9999 Password input settings