Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
136
of 208
4.3
The wake up frequency must be higher than sleep frequency.
Figure 62: Wake up/ sleep frequency
When output frequency ≤ sleep frequency ZP1384– (f
sleep
) and time > detection time
ZP1383–, it will go in sleep mode.
When min. output frequency ≤
PID frequency ≤ lower bound of frequency and sleep func-
tion is enabled (output frequency ≤
sleep frequency and time > detection time), frequency
will be 0 (in sleep mode). If sleep function is disabled, frequency command = lower bound
frequency.
When PID frequency < min. output frequency and sleep function is enabled (output fre-
quency sleep frequency and time > detection time), output frequency = 0 (in sleep mode).
If output frequency ≤
sleep frequency but time < detection time, frequency command =
lower frequency. If sleep function is disabled, output frequency =0.
P1384
This parameter sets the sleep frequency, for further information see ZP1383–.
P1384
PID Stand-by Abschalt-Frequenz 0.00 to 600.00 Hz
EE PID sleep frequency 0.00
STOP BM_u_SleepFrequency 100:1 Hz -