EasyManua.ls Logo

Baumuller b maXX 1000 - Page 98

Baumuller b maXX 1000
210 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
98
of 208
4.3
P1135
Please note the ACI/AVI switch on the b maXX
®
1000, see ZP1129from page 96.
For further information see ZFigure 44 and ZFigure 45on page 95.
P1136
Please note the ACI/AVI switch on the b maXX
®
1000, see ZP1129from page 96.
For further information see ZFigure 44 and ZFigure 45on page 95.
P1137
Please note the ACI/AVI switch on the b maXX
®
1000, see ZP1129from page 96.
For further information see ZFigure 44 and ZFigure 45on page 95.
P1138
This parameter selects the target of the analog input function.
P1135
Minimale AVI2 Frequenz 0.0 to 100.0 %
EE Minimum AVI2 frequency 0.0 %
STOP BM_u_MinimumAVI2Frequency 10:1
P1136
Maximale AVI2 Spannung 0.0 to 10.0 V
EE Maximum AVI2 voltage 0.1 V
STOP BM_u_MaximumAVI2Voltage 10:1
P1137
Maximale AVI2 Frequenz 0.0 to 100.0 %
EE Maximum AVI2 frequency 0.0 %
STOP BM_u_MaximumAVI2Frequency 10:1
P1138
AI1 Funktionsauswahl 0 to 5
EE AI1 function selection 0
STOP BM_u_AI1FunctionSelection 1:1 -
Value Meaning
0 Disable
1 First frequency source
2 Second frequency source
3 PID set point (PID enable)
4 PID positive feedback
5 PID negative feedback

Table of Contents

Related product manuals