177.34 n/Q set value unfiltered
DINT -32768 to 32767
Input value of the volume set value. Display in the ProDrive depending on the settings of
page „Servo pump - general“ in rpm or in l/min.
Scaling: 32767 Inc = Motor maximum speed * 2
177.35 n/Q set value filtered
DINT -32768 to 32767
Input value of the volume set value. Display in the ProDrive depending on the settings of
page „Servo pump - general“ in rpm or in l/min.
Scaling: 32767 Inc = Motor maximum speed * 2
177.38 n/Q Threshold
DS-support DINT 0 to 16383
As from this threshold the input value starts to function. Display in the ProDrive depending
on the settings of page „Servo pump - general“ in rpm or in l/min.
Scaling: 32767 Inc = Motor maximum speed * 2
177.39 n/Q Maximum
DS-support INT 0 to 16383
Upper limit in order to reach the maximum speed. Display in ProDrive depending on the
settings of page „Servo pump - general“ in rpm or in l/min.
Scaling: 32767 Inc = Motor maximum speed * 2
177.40 n/Q scaling divisor
DS-support INT 1 to 16383
Scaling divisor for „n/Q set value scaled“ (ZP177.41–). When scaling ensure that in the
case of max. volume set value default the „n/Q set value scaled“ (ZP177.41–) does not
exceed the maximum motor speed of the drive.
Scaling: 1000:1