-49- © BEKA 2019 All rights reserved!
BAL_ZEPTO_1019DE_EN.docx
Level prewarning
(permanent display)
o The inserted cartridge becomes empty
Insert new cartridge and reset level prewarning (see
chapter 11.5 “Level prewarning)
Motor error
o The motor or the control in the device is defective
Renew device
Overvoltage error
o The supplied operating voltage is too high (> 30 V)
Lower operating voltage
Undervoltage error
o The supplied operating voltage is too low (< 9 V)
Raise operating voltage
Temperature error
o The device is operated outside the indicated temperature
range
Heat or cool the device
Overpressure error (program P2)
o Program P2 is active and the device receives a signal
because no sensor is connected or the connected sensor
is defective
Connect the sensor or check the connected sensor
and renew it if necessary
o Program P2 is active and the device receives a signal
because the pressure in the system has exceeded 290 bar
and the pressure limiting valve has opened
Check system for blockades and leakages and
eliminate them
Pulse error (program P3)
o Program P3 is active, but the device receives no pulse
signal because no sensor is connected or the connected
sensor is defective
Connect the sensor or check the connected sensor
and renew it if necessary
o Program P3 is active, but the device receives no pulse
signal because there is a blockade in the lubrication
system
Check system for blockades and leakages and
eliminate them