operation of the equipment, failing which any losses caused by the quality of power supply,
especially property damage, personal injury, production losses and other risks, shall not be liable by Bodor. shall be solely
borne by the user, for which Bodor shall not be liable.
Ground protection
Grounding point:
1) The machine tool is grounded separately;
2) The electric control cabinet is grounded separately;
3) The peripheral equipment is grounded separately (laser, water cooler, transformer, voltage regulator, fan, smoke purifier,
etc.); the grounding resistance is required to be <4Ω.
Ground pile requirements:
The grounding device shall be made of steel. Which can use 50mm diameter steel pipe or 50mm×50mm×5mm angle steel.
While pouring an appropriate amount of saline, the angle steel and steel pipe grounding body should be vertically arranged.
A copper core cable of 10 mm² should be used as the grounding lead to ensure a good grounding effect, of which leads
should be connected to the grounding body, and for the remaining equipment, it is required to use a copper core cable that is
not less than the ground wire diameter of total power cord of the Equipment as the ground lead, with M12 bolts, and the
bolted parts shall be supplemented with anticorrosive paint.
The grounding part of electrical equipment shall be connected to the grounding trunk with a separate ground lead.
In a grounding system, the grounding resistance shall be less than or equal to 4Ω, and the repeated grounding resistance