30 en | Programming NurseCall Main Unit
F.01U.252.699 | V1.1 | 2012.01 User Manual Bosch Security Systems
Specific parameter for POCSAG
Enter the digit for the POCSAG system address. Choose from 4 and 9. Default value is 4.
Change the value of the digit with and . Confirm with .
Specific parameter for DeTeWe
Enter the first digit for the DeTeWe system address. Choose from 1 and 9. Default value is 1.
Change the value of the digit with and . Confirm with .
Example of filtering with ESPA 4.4.4.
– Display mode FR,RO,BE with Locating mode ON
– Criterion filtering: 2 characters and 1 space
– Display mode filtering: 1 character + 1 space for the floor number
2 characters + 0 space for the room number
2 characters for the bed number
– Locating mode filtering:
6 spaces between bed number and POS xyz.
In this example, a call for help from floor 008, room 023, bed 1 with the actual position 248
will generate the following sequence: "HE_8_2301______POS_248".
¬ ADDRESS -->001·xxx
¬ 1.NUM ---> 1
CR <-
CRIT 02 + 1 SPACES
INFO.: f rr0b
FL:1+1 +RO:2+0 +BE:2
BE POS xyz
SPACES : 6