Clause / Requirement Compliance Signature
voice alarm condition; The voice alarm condition is
indicated on each call station
(system status LED), remote control
or fireman’s panel and on the display
of the controller This system wide
indication can be combined with the
indication of the fault warning
condition: the controller gives an
audible warning on EMG condition
that has priority over the audible
fault signal. EMG condition is
indicated by a red LED, faults by
corresponding yellow LEDs,
therefore both conditions can be
indicated simultaneously.
fault warning condition; The fault warning condition is
indicated on each call station
(system status LED), remote control
or fireman’s panel and on the display
of the controller (faults menu). This
system wide indication can be
combined with the indication of the
voice alarm condition The display of
the controller can indicate both the
voice alarm condition and the fault
warning.
disablement condition (option with
requirements).
The optional disablement condition
is not implemented in Plena Voice
Alarm System.
5.2 Indication display Plena Voice Alarm System is
compliant.
All mandatory indications shall be
clearly identifiable, except where
otherwise specified in this European
Standard.
The Plena Voice Alarm System uses
the following color coding for
indications throughout the system:
Green: system ok
Red: system/zone in voice alarm
condition
Yellow: system in fault warning
condition
5.3 Indication on alphanumeric
displays
Not applicable.
142 en | Appendices Plena