6 The quiescent condition
Clause / Requirement Compliance Signature
Any kind of system information may be
displayed during the quiescent
condition. However, no indications shall
be given which could be confused with
indications used in the
Plena Voice Alarm System is
compliant.
voice alarm condition, If the Plena Voice Alarm System
enters the voice alarm condition,
controller, remote control panels
(including fireman’s panel), and each
call station will show a red system
status LED. In the quiescent
condition no red indicators are used
at all and the display of the
controller will never automatically
switch to the emergency menu.
fault warning condition, If the Plena Voice Alarm System
enters the fault warning condition
each call station will show a yellow
fault LED. Yellow LEDs are solely
used for fault condition.
disablement condition (option with
requirements).
The disablement condition is not
implemented in Plena Voice Alarm
System.
7 The voice alarm condition
Clause / Requirement
Compliance Signature
7.1 Reception and processing of fire
signals
Plena Voice Alarm System is
compliant.
7.1.1 The VACIE shall be capable of
receiving and processing alarm signals
from the CIE or from manual control on
the VACIE or both, and causing the
appropriate voice alarm outputs to be
activated within 3 s or on expiry of any
delay period (see 7.4).
Alarm signals from the CIE can be
received from input contacts and the
Open Interface. Manual control is
possible via the controls and input
contacts. Note the call stations are
not part of the voice alarm function
and are disabled in the alarm
condition.
144 en | Appendices Plena
2013.07 | V2.0 | Installation and Operation manual Bosch Security Systems B.V.