Clause / Requirement Compliance Signature
b manual controls at access level 1 shall
be accessible without special
procedures;
Manual controls of the Plena Voice
Alarm System at access level 1 are
accessible without special
procedures.
c indications and manual controls that
are mandatory at access level 1 shall
also be accessible at access level 2;
All Plena Voice Alarm System
indications (LEDs, equipment
connected to output contacts,
front panel display) and manual
controls (input contacts, call
station keys, front panel menus)
that are accessible at access level
1 will also be accessible at access
level 2. It may be needed to iinstal
the equipment in a 19”rack with a
glass door.
d entry to access level 2 shall be
restricted by a special procedure;
Physical access control by means
of installing the system elements in
a restricted environment, such as
placing (parts of the) 19”-units in a
19”-rack with key lock will be
needed.
e entry to access level 3 shall be
restricted by a special procedure,
differing from that for access level 2;
Entry to access level 3 is restricted
by a special procedure, see
clause13.6, access level 3
description for details. Correct
configuration and installation
(physical access control) will
ensure that the special procedure
differs from that of access level 2.
The installer should ensure that
the physical access procedure
differs from that of the physical
access procedure of access level 2,
if applicable.
f the entry to access level 4 shall be
restricted by special means which are
not part of the VACIE.
Entry to access level 4 is restricted
by means of having to use the File
Transfer Application (FTA), see
clause13.6, access level 4
description for details. This FTA is
only used for access level 4
functions and is therefore not part
of the daily operation/
configuration of the Plena Voice
Alarm System.
176 en | Appendices Plena