EasyManua.ls Logo

Bosch PRAESENSA PRA-CSLD - System Security; Change User Name and Passphrase; Reconnect Factory Default Devices

Bosch PRAESENSA PRA-CSLD
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PRAESENSA Security | en 113
Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20
7.1 System security
1. Below the Security page, click System security:
A new screen OMNEO system security appears where the:
OMNEO security username, and the
OMNEO passphrase can be viewed. These are both automatically created at 1
st
time /
initial
Logon the application, page 35
.
2. Both credentials are used to create a secure connection between the PRAESENSA
system controller, the other network devices, PC and during upgrade of the PRAESENSA
network devices firmware.
3. See
Change user name and passphrase, page 113
if you want to change the credentials.
4. See 1
st
time / initial
Logon the application, page 35
for the automatically generated
secured credentials.
5. See
Check/Upload the devices firmware, page 20
for a secured device firmware upload
connection.
6. See
Backup and restore, page 103
for a (secured) backup and restore of your
configuration file.
7.1.1 Change user name and passphrase
The security user name and passphrase are automatically generated and created at 1
st
time /
initial logon. See
Logon the application, page 35
, if required.
To change:
1. Below the System security page, click the + of the Change user name and passprase
category row:
Make sure that all configured network devices are connected. See also
Show
disconnected devices, page 114
.
2. Click the Generate (recommended) button which will generate a new User name and
Passphrase or enter a new User name (minimum 5 and maximum 32 characters) and
Passphrase (minimum 8 and maximum 64 characters):
IMPORTANT: for security reasons, both the User name and Passphrase need to be
changed.
3. Click the Change button:
IMPORTANT: Devices that get disconnected during the change process will still
receive the changes upon reconnection within one hour. After one hour, remaining
devices must first be reset to factory default, and then reconnected. See
Reconnect
factory default devices, page 113
.
Refer to
User accounts, page 38
7.1.2 Reconnect factory default devices
Use this function if you want to securely reconnect one or more factory default devices. Notice
that reconnect a network device only works when it was already added in
System
composition, page 40
.
To do so:
1. Reset the disconnected device(s) to default by using the reset to default button:
For location of the reset to default button of the individual devices, see
Device
options, page 43
> <device name> > Rear panel indicators and controls and/or the
PRAESENSA installation manual.